Electrical calculator (cable calculator): work out voltage drop and cable size
Cable calculator: enter power and cable length – voltage drop, cable size and power with a traffic light for the limit value.
In short Example (1~ 230 V · 3.5 kW · 25 m copper 2.5 mm²): Voltage drop 2.36 %, ΔU 5.43 V at 15.22 A. Rule: ΔU = 2 × L × I × cos φ ÷ (κ × A), preset limit value 3%.
An example step by step
1~ 230 V · 3.5 kW · 25 m copper 2.5 mm²
- 1CurrentI = 3,500 W ÷ (230 V × 1.00) = 15.22 A
- 2Voltage dropΔU = 2 × 25 m × 15.22 A × 1.00 ÷ (56 × 2.5 mm²) = 5.43 V
- 3As a percentage5.43 V ÷ 230 V = 2.36%
- 4Factor2 for alternating current (outgoing and return conductor), L is the one-way length
- Result: 2.36 %
How we calculate
Current single-phase: I = P ÷ (U × cos φ); three-phase: I = P ÷ (√3 × U × cos φ).
Voltage drop single-phase: ΔU = 2 × L × I × cos φ ÷ (κ × A); three-phase: ΔU = √3 × L × I × cos φ ÷ (κ × A). L is the one-way cable length, κ the conductivity (copper 56, aluminium 35 m/(Ω·mm²)), A the cross-sectional area in mm². In per cent: ΔU ÷ U × 100.
Minimum cable size = 2 × L × I × cos φ ÷ (κ × permitted voltage drop × U), for three-phase with √3 instead of 2. The result is rounded up to the next standard cable size.
The traffic light is green below 80% of the limit value, amber between 80 and 100%, red above.
Important: The calculator does not check current-carrying capacity or the protective device. A qualified electrician must do that.
Voltage drop by cable length and cross-section
The table shows the voltage drop ΔU in per cent for a single-phase cable at 230 V, copper and 16 A, by one-way cable length and cross-section.
| Length | 1,5 mm² | 2,5 mm² | 4 mm² | 6 mm² |
|---|---|---|---|---|
| 10 m | 1.7 % | 1.0 % | 0.6 % | 0.4 % |
| 25 m | 4.1 % * | 2.5 % | 1.6 % | 1.0 % |
| 40 m | 6.6 % * | 4.0 % * | 2.5 % | 1.7 % |
| 60 m | 9.9 % * | 6.0 % * | 3.7 % * | 2.5 % |
* = above the limit value of 3% preset in the calculator. The table shows only the voltage drop, not current-carrying capacity: cross-section, installation method and protective device are checked by a qualified electrician. For guidance only.
Cable calculator app
Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.
- Projects & rooms
- PDF with logo
- Your own defaults
- Offline, no account
Common questions
How do you calculate voltage drop?
Single-phase with ΔU = 2 × L × I × cos φ ÷ (κ × A). L is the one-way length; the factor 2 stands for the outgoing and return conductor. In the example: 15.22 A over 25 m of copper at 2.5 mm² gives 5.43 V, which is 2.36%.
What voltage drop is permitted?
In the calculator 3% is preset and you can change the value. Standards, the network operator’s requirements and the design are what count. If in doubt, ask a qualified electrician.
Is the cable length one-way or there and back?
Enter the one-way length from the consumer unit to the load. The calculator allows for the outgoing and return conductor itself with the factor 2 (single-phase) or √3 (three-phase).
Is the minimum cable size enough for the protective device?
Not necessarily. The calculator only checks the voltage drop. Current-carrying capacity, installation method and protective device must be checked separately.
Can I use the calculator for aluminium cables?
Yes. Choose aluminium (κ = 35) instead of copper (κ = 56). You enter your own κ values under ‘Advanced’.
What does the traffic light mean?
Green below 80% of the limit value, amber 80–100%, red above. A symbol and text also show the status.
Does the calculator replace the design?
No. For guidance only – design and installation exclusively by a qualified electrician.
Which cable size for how many kW?
The voltage drop depends not on power alone but on current and length. Example: 3.5 kW at 230 V and 25 m of copper – the minimum cable size by voltage drop alone (3%) is 2.5 mm². Current-carrying capacity and protective device are additionally checked by a qualified electrician; for guidance only.
What is the maximum length of a 2.5 mm² cable?
Based on voltage drop only: at 16 A, 230 V and copper, a 2.5 mm² cable stays below 3% up to about 30 m one-way length. The current-carrying capacity is not checked by this.