Electrical calculator (cable calculator): work out voltage drop and cable size

Cable calculator: enter power and cable length – voltage drop, cable size and power with a traffic light for the limit value.

In short Example (1~ 230 V · 3.5 kW · 25 m copper 2.5 mm²): Voltage drop 2.36 %, ΔU 5.43 V at 15.22 A. Rule: ΔU = 2 × L × I × cos φ ÷ (κ × A), preset limit value 3%.

An example step by step

1~ 230 V · 3.5 kW · 25 m copper 2.5 mm²

  1. 1
    CurrentI = 3,500 W ÷ (230 V × 1.00) = 15.22 A
  2. 2
    Voltage dropΔU = 2 × 25 m × 15.22 A × 1.00 ÷ (56 × 2.5 mm²) = 5.43 V
  3. 3
    As a percentage5.43 V ÷ 230 V = 2.36%
  4. 4
    Factor2 for alternating current (outgoing and return conductor), L is the one-way length
  5. Result: 2.36 %

How we calculate

Current single-phase: I = P ÷ (U × cos φ); three-phase: I = P ÷ (√3 × U × cos φ).

Voltage drop single-phase: ΔU = 2 × L × I × cos φ ÷ (κ × A); three-phase: ΔU = √3 × L × I × cos φ ÷ (κ × A). L is the one-way cable length, κ the conductivity (copper 56, aluminium 35 m/(Ω·mm²)), A the cross-sectional area in mm². In per cent: ΔU ÷ U × 100.

Minimum cable size = 2 × L × I × cos φ ÷ (κ × permitted voltage drop × U), for three-phase with √3 instead of 2. The result is rounded up to the next standard cable size.

The traffic light is green below 80% of the limit value, amber between 80 and 100%, red above.

Important: The calculator does not check current-carrying capacity or the protective device. A qualified electrician must do that.

Voltage drop by cable length and cross-section

The table shows the voltage drop ΔU in per cent for a single-phase cable at 230 V, copper and 16 A, by one-way cable length and cross-section.

Voltage drop in per cent at 230 V, copper, 16 A, by one-way length and cross-section
Length1,5 mm²2,5 mm²4 mm²6 mm²
10 m1.7 %1.0 %0.6 %0.4 %
25 m4.1 % *2.5 %1.6 %1.0 %
40 m6.6 % *4.0 % *2.5 %1.7 %
60 m9.9 % *6.0 % *3.7 % *2.5 %

* = above the limit value of 3% preset in the calculator. The table shows only the voltage drop, not current-carrying capacity: cross-section, installation method and protective device are checked by a qualified electrician. For guidance only.

The calculator app

Cable calculator app

Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.

  • Projects & rooms
  • PDF with logo
  • Your own defaults
  • Offline, no account
FreeGet the app free · Pro features one-off for £4.99, no subscription
Coming soon on theApp StoreGet it onGoogle Play
The app is free and calculates fully without Pro. Pro unlocks saving, projects and PDF.

Common questions

How do you calculate voltage drop?

Single-phase with ΔU = 2 × L × I × cos φ ÷ (κ × A). L is the one-way length; the factor 2 stands for the outgoing and return conductor. In the example: 15.22 A over 25 m of copper at 2.5 mm² gives 5.43 V, which is 2.36%.

What voltage drop is permitted?

In the calculator 3% is preset and you can change the value. Standards, the network operator’s requirements and the design are what count. If in doubt, ask a qualified electrician.

Is the cable length one-way or there and back?

Enter the one-way length from the consumer unit to the load. The calculator allows for the outgoing and return conductor itself with the factor 2 (single-phase) or √3 (three-phase).

Is the minimum cable size enough for the protective device?

Not necessarily. The calculator only checks the voltage drop. Current-carrying capacity, installation method and protective device must be checked separately.

Can I use the calculator for aluminium cables?

Yes. Choose aluminium (κ = 35) instead of copper (κ = 56). You enter your own κ values under ‘Advanced’.

What does the traffic light mean?

Green below 80% of the limit value, amber 80–100%, red above. A symbol and text also show the status.

Does the calculator replace the design?

No. For guidance only – design and installation exclusively by a qualified electrician.

Which cable size for how many kW?

The voltage drop depends not on power alone but on current and length. Example: 3.5 kW at 230 V and 25 m of copper – the minimum cable size by voltage drop alone (3%) is 2.5 mm². Current-carrying capacity and protective device are additionally checked by a qualified electrician; for guidance only.

What is the maximum length of a 2.5 mm² cable?

Based on voltage drop only: at 16 A, 230 V and copper, a 2.5 mm² cable stays below 3% up to about 30 m one-way length. The current-carrying capacity is not checked by this.