Voltage drop calculator: ΔU in volts and per cent
Enter the load, cable length and cross-section – the voltage drop appears instantly with a traffic light.
In short With 3.5 kW (1~, 230 V, cos φ 1.0), 25 m one-way length, copper and 2.5 mm² the result is a current of 15.22 A and a voltage drop of 5.43 V, which is 2.36% – Voltage drop: 2.36%. Calculation steps: Current, I = 3,500 W ÷ (230 V × 1.00) = 15.22 A.
An example step by step
With 3.5 kW (1~, 230 V, cos φ 1.0), 25 m one-way length, copper and 2.5 mm² the result is a current of 15.22 A and a voltage drop of 5.43 V, which is 2.36%.
- 1CurrentI = 3,500 W ÷ (230 V × 1.00) = 15.22 A
- 2Voltage dropΔU = 2 × 25 m × 15.22 A × 1.00 ÷ (56 × 2.5 mm²) = 5.43 V
- 3As a percentage5.43 V ÷ 230 V = 2.36%
- 4Factor2 for alternating current (outgoing and return conductor), L is the one-way length
- Result: Voltage drop: 2.36%
Voltage drop at 400 V three-phase by length and cross-section
With three-phase at 400 V the voltage drop in per cent is smaller than at 230 V. The table applies to copper and 16 A per line conductor.
| Length | 1,5 mm² | 2,5 mm² | 4 mm² | 6 mm² |
|---|---|---|---|---|
| 10 m | 0.82 % | 0.49 % | 0.31 % | 0.21 % |
| 25 m | 2.06 % | 1.24 % | 0.77 % | 0.52 % |
| 50 m | 4.12 % * | 2.47 % | 1.55 % | 1.03 % |
| 100 m | 8.25 % * | 4.95 % * | 3.09 % * | 2.06 % |
* = above the preset limit value of 3%. Calculated with ΔU = √3 × L × I × cos φ ÷ (κ × A), cos φ = 1. No statement on current-carrying capacity – a qualified electrician checks that. For guidance only.
Cable calculator app
Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.
- Projects & rooms
- PDF with logo
- Your own defaults
- Offline, no account
Common questions
How do you calculate voltage drop?
Single-phase with ΔU = 2 × L × I × cos φ ÷ (κ × A), three-phase with √3 instead of 2. In the example: 15.22 A over 25 m of copper at 2.5 mm² gives 5.43 V, i.e. 2.36%.
What effect does the cross-section have?
A larger cross-section lowers the voltage drop. In the example 1.5 mm² gives 3.94%, 2.5 mm² 2.36% and 4 mm² 1.48%. Aluminium at 2.5 mm² would give 3.78%.
Is the cable length one-way or there and back?
Enter the one-way length from the consumer unit to the load. The calculator itself allows for the outgoing and return conductor with the factor 2 (single-phase) or √3 (three-phase).
What voltage drop is permitted?
In the calculator 3% is preset and you can change the limit value. Standards and the network operator’s requirements are what count. The traffic light only shows the distance to your limit value, nothing more.
Is a small voltage drop enough for safety?
No. The calculator only checks the voltage drop. Current-carrying capacity, installation method and protective device must be checked separately; that is the job of a qualified electrician. The results are guide values, not approval of an installation.
How much voltage drop is permitted at 230 V and 400 V?
In the calculator 3% is preset: that is 6.9 V at 230 V and 12 V at 400 V. Standards and the network operator are what count; if in doubt, ask a qualified electrician.
How far can I run a 4 mm² cable at 16 A?
By voltage drop alone: at 230 V, copper and 16 A a 4 mm² cable stays below 3% up to about 48 m one-way length. The calculator does not check current-carrying capacity.