Cable size calculator for 12 V, 24 V and 48 V
Enter the voltage, load, one-way cable length and permitted voltage drop – the calculator gives the calculated minimum cable size for direct current, for the voltage drop only. A qualified electrician clarifies current-carrying capacity, installation method and protection.
In short At 12 V, 240 W (20 A), 5 m one-way length, copper and a 3% limit value, at least 9.92 mm² is needed by calculation for the voltage drop; the next standard size is 10 mm² (ΔU 0.36 V, which is 2.98%). This is not a cable recommendation – Minimum cable size (voltage drop): 9.92 mm². Calculation steps: Current, I = 240 W ÷ 12 V = 20.00 A.
An example step by step
At 12 V, 240 W (20 A), 5 m one-way length, copper and a 3% limit value, at least 9.92 mm² is needed by calculation for the voltage drop; the next standard size is 10 mm² (ΔU 0.36 V, which is 2.98%). This is not a cable recommendation.
- 1CurrentI = 240 W ÷ 12 V = 20.00 A
- 2Minimum cable sizeA = 2 × 5 m × 20.00 A × 1.00 ÷ (56 × 3% × 12 V) = 9.92 mm² → 10 mm²
- 3Voltage dropΔU = 2 × 5 m × 20.00 A × 1.00 ÷ (56 × 10 mm²) = 0.36 V
- 4As a percentage0.36 V ÷ 12 V = 2.98%
- 5Factor2 for direct current (outgoing and return conductor), L is the one-way length
- Result: Minimum cable size (voltage drop): 9.92 mm²
How we calculate
With direct current there is no phase angle: cos φ is 1 and the current flows through outgoing and return conductors. The single-phase formula with factor 2 therefore applies, only with the chosen operating voltage instead of 230 V. L is the one-way length from the source to the load.
I = P ÷ U
ΔU = 2 × L × I ÷ (κ × A)
A = 2 × L × I ÷ (κ × ΔU permitted) with ΔU permitted = limit in % × U
The conductivity κ is 56 for copper and 35 m/(Ω·mm²) for aluminium. The calculator rounds up to the next standard size from 1.5 to 120 mm². Because the permitted voltage drop is small in absolute terms (3% of 12 V is only 0.36 V), 12 V cables need a much larger cross-section than 230 V cables of the same power.
Same power, different voltage
Load 240 W, 5 m one-way length, copper, limit 3%: at double the voltage the current halves and the cross-section drops to a quarter.
| Voltage | Current I | Minimum cable size | Standard size | ΔU in % at standard size |
|---|---|---|---|---|
| 12 V | 20.0 A | 9.92 mm² | 10 mm² | 2.98 % |
| 24 V | 10.0 A | 2.48 mm² | 2.5 mm² | 2.98 % |
| 48 V | 5.0 A | 0.62 mm² | 1.5 mm² | 1.24 % |
Effect of cable length at 12 V
Load 240 W (20 A) at 12 V, copper, limit 3%: the minimum cable size grows linearly with the length.
| One-way length | Minimum cable size | Standard size | ΔU at standard size | ΔU in % |
|---|---|---|---|---|
| 2 m | 3.97 mm² | 4 mm² | 0.36 V | 2.98 % |
| 5 m | 9.92 mm² | 10 mm² | 0.36 V | 2.98 % |
| 10 m | 19.84 mm² | 25 mm² | 0.29 V | 2.38 % |
| 15 m | 29.76 mm² | 35 mm² | 0.31 V | 2.55 % |
Cable calculator app
Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.
- Projects & rooms
- PDF with logo
- Your own defaults
- Offline, no account
Common questions
How do I calculate the cable size at 12 V?
With A = 2 × L × I ÷ (κ × permitted voltage drop in V). In the example: 2 × 5 m × 20 A ÷ (56 × 0.36 V) = 9.92 mm², rounded up to 10 mm².
Why does 12 V need so much more cross-section than 230 V?
The same power needs around 19 times as much current at 12 V as at 230 V, and the permitted voltage drop is tiny in volts: 3% of 12 V is only 0.36 V, whereas for 230 V it is 6.9 V.
What voltage drop is permitted?
The calculator offers 1, 2, 3 and 5% to choose from, with 3% preset. Sensitive loads and inverters often require less. The information from the device or battery manufacturer and the applicable standards are what count.
What changes at 24 V and 48 V?
For the same power the current falls in proportion to the voltage. For 240 W over 5 m this gives 10 mm² at 12 V, 2.5 mm² at 24 V and 1.5 mm² at 48 V (3% each time, copper).
Is the length one-way or there and back?
Enter the one-way length from the source to the load. The calculator itself allows for the positive and negative cable with the factor 2.
Is the calculated cross-section enough for the protective device and current?
No. The calculator only checks the voltage drop. Current-carrying capacity, installation method and protection must be checked separately; that is the job of a qualified electrician. The results are guide values.