Cable size calculator for 12 V, 24 V and 48 V

Enter the voltage, load, one-way cable length and permitted voltage drop – the calculator gives the calculated minimum cable size for direct current, for the voltage drop only. A qualified electrician clarifies current-carrying capacity, installation method and protection.

In short At 12 V, 240 W (20 A), 5 m one-way length, copper and a 3% limit value, at least 9.92 mm² is needed by calculation for the voltage drop; the next standard size is 10 mm² (ΔU 0.36 V, which is 2.98%). This is not a cable recommendation – Minimum cable size (voltage drop): 9.92 mm². Calculation steps: Current, I = 240 W ÷ 12 V = 20.00 A.

An example step by step

At 12 V, 240 W (20 A), 5 m one-way length, copper and a 3% limit value, at least 9.92 mm² is needed by calculation for the voltage drop; the next standard size is 10 mm² (ΔU 0.36 V, which is 2.98%). This is not a cable recommendation.

  1. 1
    CurrentI = 240 W ÷ 12 V = 20.00 A
  2. 2
    Minimum cable sizeA = 2 × 5 m × 20.00 A × 1.00 ÷ (56 × 3% × 12 V) = 9.92 mm² → 10 mm²
  3. 3
    Voltage dropΔU = 2 × 5 m × 20.00 A × 1.00 ÷ (56 × 10 mm²) = 0.36 V
  4. 4
    As a percentage0.36 V ÷ 12 V = 2.98%
  5. 5
    Factor2 for direct current (outgoing and return conductor), L is the one-way length
  6. Result: Minimum cable size (voltage drop): 9.92 mm²

How we calculate

With direct current there is no phase angle: cos φ is 1 and the current flows through outgoing and return conductors. The single-phase formula with factor 2 therefore applies, only with the chosen operating voltage instead of 230 V. L is the one-way length from the source to the load.

I = P ÷ U

ΔU = 2 × L × I ÷ (κ × A)

A = 2 × L × I ÷ (κ × ΔU permitted) with ΔU permitted = limit in % × U

The conductivity κ is 56 for copper and 35 m/(Ω·mm²) for aluminium. The calculator rounds up to the next standard size from 1.5 to 120 mm². Because the permitted voltage drop is small in absolute terms (3% of 12 V is only 0.36 V), 12 V cables need a much larger cross-section than 230 V cables of the same power.

Same power, different voltage

Load 240 W, 5 m one-way length, copper, limit 3%: at double the voltage the current halves and the cross-section drops to a quarter.

VoltageCurrent IMinimum cable sizeStandard sizeΔU in % at standard size
12 V20.0 A9.92 mm²10 mm²2.98 %
24 V10.0 A2.48 mm²2.5 mm²2.98 %
48 V5.0 A0.62 mm²1.5 mm²1.24 %

Effect of cable length at 12 V

Load 240 W (20 A) at 12 V, copper, limit 3%: the minimum cable size grows linearly with the length.

One-way lengthMinimum cable sizeStandard sizeΔU at standard sizeΔU in %
2 m3.97 mm²4 mm²0.36 V2.98 %
5 m9.92 mm²10 mm²0.36 V2.98 %
10 m19.84 mm²25 mm²0.29 V2.38 %
15 m29.76 mm²35 mm²0.31 V2.55 %
Full calculatorCable calculatorGo to Cable calculator
The calculator app

Cable calculator app

Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.

  • Projects & rooms
  • PDF with logo
  • Your own defaults
  • Offline, no account
FreeGet the app free · Pro features one-off for £4.99, no subscription
Coming soon on theApp StoreGet it onGoogle Play
The app is free and calculates fully without Pro. Pro unlocks saving, projects and PDF.

Common questions

How do I calculate the cable size at 12 V?

With A = 2 × L × I ÷ (κ × permitted voltage drop in V). In the example: 2 × 5 m × 20 A ÷ (56 × 0.36 V) = 9.92 mm², rounded up to 10 mm².

Why does 12 V need so much more cross-section than 230 V?

The same power needs around 19 times as much current at 12 V as at 230 V, and the permitted voltage drop is tiny in volts: 3% of 12 V is only 0.36 V, whereas for 230 V it is 6.9 V.

What voltage drop is permitted?

The calculator offers 1, 2, 3 and 5% to choose from, with 3% preset. Sensitive loads and inverters often require less. The information from the device or battery manufacturer and the applicable standards are what count.

What changes at 24 V and 48 V?

For the same power the current falls in proportion to the voltage. For 240 W over 5 m this gives 10 mm² at 12 V, 2.5 mm² at 24 V and 1.5 mm² at 48 V (3% each time, copper).

Is the length one-way or there and back?

Enter the one-way length from the source to the load. The calculator itself allows for the positive and negative cable with the factor 2.

Is the calculated cross-section enough for the protective device and current?

No. The calculator only checks the voltage drop. Current-carrying capacity, installation method and protection must be checked separately; that is the job of a qualified electrician. The results are guide values.