Cable size calculator: minimum cable size for the voltage drop
Enter the load, cable length and permitted voltage drop – the minimum cable size appears instantly.
In short At 11 kW (3~, 400 V, cos φ 1.0), 40 m one-way length, copper and a 3% limit value, 15.88 A flows. For the voltage drop at least 1.64 mm² is needed by calculation; the next standard size is 2.5 mm² (ΔU 1.96%). This is not a cable recommendation – Minimum cable size (voltage drop): 1.64 mm². Calculation steps: Current, I = 11,000 W ÷ (√3 × 400 V × 1.00) = 15.88 A.
An example step by step
At 11 kW (3~, 400 V, cos φ 1.0), 40 m one-way length, copper and a 3% limit value, 15.88 A flows. For the voltage drop at least 1.64 mm² is needed by calculation; the next standard size is 2.5 mm² (ΔU 1.96%). This is not a cable recommendation.
- 1CurrentI = 11,000 W ÷ (√3 × 400 V × 1.00) = 15.88 A
- 2Minimum cable sizeA = √3 × 40 m × 15.88 A × 1.00 ÷ (56 × 3% × 400 V) = 1.64 mm² → 2.5 mm²
- 3Voltage dropΔU = √3 × 40 m × 15.88 A × 1.00 ÷ (56 × 2.5 mm²) = 7.86 V
- 4As a percentage7.86 V ÷ 400 V = 1.96%
- 5Factor√3 for three-phase
- Result: Minimum cable size (voltage drop): 1.64 mm²
Voltage drop per amp and 10 m by cable cross-section
With this value you can quickly work out the voltage drop for any cable cross-section: voltage drop = value × current in A × length in m ÷ 10.
| Cross-section | Copper | Aluminium |
|---|---|---|
| 1.5 mm² | 0.238 V | 0.381 V |
| 2.5 mm² | 0.143 V | 0.229 V |
| 4 mm² | 0.089 V | 0.143 V |
| 6 mm² | 0.060 V | 0.095 V |
| 10 mm² | 0.036 V | 0.057 V |
| 16 mm² | 0.022 V | 0.036 V |
| 25 mm² | 0.014 V | 0.023 V |
Example: 16 A over 25 m of copper at 2.5 mm²: 0.143 V × 16 × 2.5 = 5.7 V. The table shows only the voltage drop, not current-carrying capacity; cross-section and protective device are checked by a qualified electrician. For guidance only.
Cable calculator app
Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.
- Projects & rooms
- PDF with logo
- Your own defaults
- Offline, no account
Common questions
How do I calculate the cable size?
From current, one-way length, material and permitted voltage drop: A = √3 × L × I × cos φ ÷ (κ × permitted voltage drop in V) for three-phase. In the example 1.64 mm²; the calculator also gives the next standard size, 2.5 mm².
Is the result the cable size I should install?
No. It is only the minimum cable size for the voltage drop. Current-carrying capacity, installation method and protective device may require a larger cross-section and must be checked separately; that is the job of a qualified electrician.
How does the length affect it?
The minimum cable size grows with the length. In the example it is 1.64 mm² at 40 m and 3.27 mm² at 80 m.
What changes with aluminium?
Aluminium conducts less well (κ = 35 instead of 56 m/(Ω·mm²)). In the example the minimum cable size rises from 1.64 to 2.62 mm²; the next standard size is 4 mm². A qualified professional clarifies whether aluminium is permitted.
Which limit value for the voltage drop does the calculator use?
3% is preset. You can adjust the value, for example to the network operator’s or the design’s requirements.
How much voltage drop does a 1.5 mm² cable have over 10 m at 10 A?
At 230 V and copper it is 2.38 V, which is 1.04%. The current-carrying capacity is not checked by this – that is for a qualified electrician.