Cable size calculator: minimum cable size for the voltage drop

Enter the load, cable length and permitted voltage drop – the minimum cable size appears instantly.

In short At 11 kW (3~, 400 V, cos φ 1.0), 40 m one-way length, copper and a 3% limit value, 15.88 A flows. For the voltage drop at least 1.64 mm² is needed by calculation; the next standard size is 2.5 mm² (ΔU 1.96%). This is not a cable recommendation – Minimum cable size (voltage drop): 1.64 mm². Calculation steps: Current, I = 11,000 W ÷ (√3 × 400 V × 1.00) = 15.88 A.

An example step by step

At 11 kW (3~, 400 V, cos φ 1.0), 40 m one-way length, copper and a 3% limit value, 15.88 A flows. For the voltage drop at least 1.64 mm² is needed by calculation; the next standard size is 2.5 mm² (ΔU 1.96%). This is not a cable recommendation.

  1. 1
    CurrentI = 11,000 W ÷ (√3 × 400 V × 1.00) = 15.88 A
  2. 2
    Minimum cable sizeA = √3 × 40 m × 15.88 A × 1.00 ÷ (56 × 3% × 400 V) = 1.64 mm² → 2.5 mm²
  3. 3
    Voltage dropΔU = √3 × 40 m × 15.88 A × 1.00 ÷ (56 × 2.5 mm²) = 7.86 V
  4. 4
    As a percentage7.86 V ÷ 400 V = 1.96%
  5. 5
    Factor√3 for three-phase
  6. Result: Minimum cable size (voltage drop): 1.64 mm²

Voltage drop per amp and 10 m by cable cross-section

With this value you can quickly work out the voltage drop for any cable cross-section: voltage drop = value × current in A × length in m ÷ 10.

Voltage drop in volts per 1 A and 10 m one-way length (single-phase) for copper and aluminium
Cross-sectionCopperAluminium
1.5 mm²0.238 V0.381 V
2.5 mm²0.143 V0.229 V
4 mm²0.089 V0.143 V
6 mm²0.060 V0.095 V
10 mm²0.036 V0.057 V
16 mm²0.022 V0.036 V
25 mm²0.014 V0.023 V

Example: 16 A over 25 m of copper at 2.5 mm²: 0.143 V × 16 × 2.5 = 5.7 V. The table shows only the voltage drop, not current-carrying capacity; cross-section and protective device are checked by a qualified electrician. For guidance only.

The calculator app

Cable calculator app

Checks voltage drop, cable size and power – with a traffic light for the limit value. In the browser you check one cable – in the app whole circuits and cable lists, with a PDF for your customers.

  • Projects & rooms
  • PDF with logo
  • Your own defaults
  • Offline, no account
FreeGet the app free · Pro features one-off for £4.99, no subscription
Coming soon on theApp StoreGet it onGoogle Play
The app is free and calculates fully without Pro. Pro unlocks saving, projects and PDF.

Common questions

How do I calculate the cable size?

From current, one-way length, material and permitted voltage drop: A = √3 × L × I × cos φ ÷ (κ × permitted voltage drop in V) for three-phase. In the example 1.64 mm²; the calculator also gives the next standard size, 2.5 mm².

Is the result the cable size I should install?

No. It is only the minimum cable size for the voltage drop. Current-carrying capacity, installation method and protective device may require a larger cross-section and must be checked separately; that is the job of a qualified electrician.

How does the length affect it?

The minimum cable size grows with the length. In the example it is 1.64 mm² at 40 m and 3.27 mm² at 80 m.

What changes with aluminium?

Aluminium conducts less well (κ = 35 instead of 56 m/(Ω·mm²)). In the example the minimum cable size rises from 1.64 to 2.62 mm²; the next standard size is 4 mm². A qualified professional clarifies whether aluminium is permitted.

Which limit value for the voltage drop does the calculator use?

3% is preset. You can adjust the value, for example to the network operator’s or the design’s requirements.

How much voltage drop does a 1.5 mm² cable have over 10 m at 10 A?

At 230 V and copper it is 2.38 V, which is 1.04%. The current-carrying capacity is not checked by this – that is for a qualified electrician.